Test your cooler sample under real operating conditions. Learn about measurement points, thermal imaging, steady-state conditions, and data logging procedures.

<svg aria-label="Prototype performance testing — schematic technical drawing" class="kb-diagram" role="img" viewbox="0 0 640 250" xmlns="http://www.w3.org/2000/svg"><rect fill="#f3f7f8" height="250" rx="10" width="640"></rect><g fill="none" stroke="#26798a" stroke-linecap="round" stroke-linejoin="round" stroke-width="2.4"><path d="M115 47v137h420" stroke="#91a3af"></path><path d="M135 170c80-10 73-82 180-91s125-8 198-8" stroke="#ba653d" stroke-width="4"></path><path d="M115 70h420" stroke="#91a3af" stroke-dasharray="5 7"></path><circle cx="454" cy="71" fill="#26798a" r="6"></circle><text class="kb-label" x="325" y="227">Time → thermal steady state</text><text class="kb-label" x="320" y="40">Schematic temperature curve · not measured data</text></g></svg>

Define acceptance criteria first

Before starting the test, define the temperature limits that must not be exceeded under specific conditions. Component junction targets, allowable case temperatures, and the limits of surrounding parts may differ. Simply stating that the "heatsink stayed cool" is not enough to prove that the design is sufficient.

Simulate the product in your test setup

Configure the enclosure, ventilation openings, mounting orientation, interface, and fasteners as close to the final product as possible. Determine the actual power dissipation of the component being tested. An initial scan using a resistive heater can be useful, but if the source area and contact conditions differ from the actual component, the results should not be directly extrapolated.

Standardize measurement points

Monitor the local air entering the heatsink, a point on the base near the source, the measurement point defined by the component manufacturer, and critical neighboring parts if necessary. Thin thermocouples must be attached without disrupting contact; the sensor mounting and cable routing should be documented. Measuring from a different point on each sample weakens the comparison.

Account for surface effects in thermal imaging

Shiny aluminum can reflect its surroundings due to its low emissivity; the value on the screen may not represent the actual surface temperature. Comparisons can be made using a reference surface with known emissivity and high temperature resistance, or by using contact measurements. The camera does not measure the internal junction temperature directly; it only provides information about the visible surface.

Monitor steady-state conditions

Record temperature over time and observe that the slope has sufficiently flattened. For example, a change of less than 1 °C over the last 10 minutes can be defined as a starting criterion in the test plan; however, this is not a universal standard, and larger thermal masses may require longer monitoring. If the ambient temperature is changing simultaneously, evaluate the temperature difference instead.

How to interpret sample results?

Hypothetically, in a steady-state test where 20 W of heat is transferred to the heatsink, the local air is 30 °C, and the representative base is 70 °C, the effective resistance is calculated as (70−30)/20 = 2 °C/W. If a significant portion of the heat is escaping through other paths, using the total electrical power in this equation will be misleading. Report the result along with the measurement point, orientation, and flow conditions.

What to include in test records

Store the date, profile code and cut length, component, interface, mounting method, power, environment, time-temperature data, and photographs. Verify the highest target ambient and load combination. Maintain a cause-and-effect relationship by changing only one variable in the next sample.

Frequently asked questions

Is a five-minute test sufficient?

It depends on the thermal time constant of the system. A fixed duration is not considered sufficient unless it is demonstrated that a steady state has been reached.

Is the heatsink temperature the same as the junction temperature?

No. Internal component and interface temperature differences must be evaluated separately.

Review the relevant profiles · Request technical support