Fan airflow and pressure

Evaluate the actual airflow at the intersection of the fan curve and system resistance; account for filter and blade effects.

<svg aria-label="Fan airflow and pressure — schematic technical drawing" class="kb-diagram" role="img" viewbox="0 0 640 250" xmlns="http://www.w3.org/2000/svg"><rect fill="#f3f7f8" height="250" rx="10" width="640"></rect><g fill="none" stroke="#26798a" stroke-linecap="round" stroke-linejoin="round" stroke-width="2.4"><path d="M145 35v150h360"></path><path d="M164 65q205 3 318 104"></path><path d="M166 172q188-8 316-120" stroke="#ba653d"></path><circle cx="361" cy="115" r="8"></circle><path d="M361 127v55M350 115H147"></path><text class="kb-label" x="320" y="226">Fan curve ∩ system resistance = operating point</text></g></svg>

The maximum flow rate in the catalog is not sufficient information

A fan's free-air flow rate refers to conditions where there is no significant flow resistance in front of it. When a housing, filter, and dense fins are added, the operating point changes. Therefore, choosing the fan with the highest flow rate does not guarantee that the most air will pass through the heatsink. It is necessary to examine the fan's pressure-flow curve together with the system's airflow path.

The operating point is the intersection of two curves

The fan curve shows the pressure it can provide relative to the flow rate. System resistance also generally increases as the flow rate increases. The point where these two relationships intersect approximately determines the actual operating condition. Check the manufacturer's measurement setup, supply voltage, and speed. It is not possible to see the regions where the fan might operate unstably from a single catalog page alone.

Preliminary sizing calculation for air

The relationship P≈ρ×cp×V̇×ΔT provides an initial estimate for heat transferred to the air. Assuming approximately ρ=1.2 kg/m³ and cp=1000 J/(kg·K), for a 100 W load and a 10 °C rise in air temperature, V̇≈0.0083 m³/s, or approximately 30 m³/h, is found. This is an ideal energy balance calculation; it does not account for bypass, hot spots, or system pressure drop on its own.

Air passing between the fins is what matters

Some of the air blown by the fan may escape around the sides of the heatsink. If the use of a duct, gasket, or shroud is required, test it in the prototype with its actual geometry. When evaluating fin spacing and cut length in fin profiles, include the airflow path in the drawing. Denser fins may offer more surface area, but when flow resistance increases, the overall result may not be as expected.

Do not forget about contamination and failure conditions

The operating point changes when the filter becomes clogged or the fan speed drops. Do not choose your design margin based solely on the initial test of a new fan. Evaluate air inlet temperature, noise, fan power, and maintenance intervals together. Make the final decision by measuring the temperature in the actual enclosure; do not directly convert catalog flow rates into heatsink performance.

Quick checklist

Frequently asked questions

Does using two fans double the flow rate?

It is generally not calculated that simply. The series or parallel arrangement and the system resistance determine the resulting operating point.